A page to track the electrical changes requested and made in rLab.

Any works carried out on the building electrical supply MUST be completed in accordance with the current version of the IET Requirements For Electrical Installations (the Electrical Regs) and by people who know what they are doing. This is one area where we do not simply 'hack the space' as the consequences of getting it wrong are too severe.

As data cabling often overlaps with the electrical installation, sharing trunking etc, it is also covered on this page.

If you have any projects that may need changes to the lab electrical system, please ask before you go ahead with the project. Anything unsafe will be removed without notice.

Planned Projects

  • Fit new overhead lighting for the kitchen table
  • Main Room re-work project - Power for the west wall, and the 3d printers
  • Test and sort out the emergency lighting
  • Install new emergency lighting for the Laser Room and back stairs
  • Sort out the main distribution boards
  • Tidy up the data rack
  • Put in a fused outlet for the Workshop air cleaner
  • Document the different distribution boards
  • Install worklight for the wood lathe
  • Install extractor fan for the Workshop
  • Connect up extractor fan in toilet
  • Move upstairs lights onto the Kitchen board

Completed Projects

  • Rewire Laser room. Install data cabling to both walls
  • Replace Workshop extension leads with durable, 13a rated leads suitable for a workshop environment
  • Install new sub-board in the Kitchen for upstairs power
  • Install new circuits in the Kitchen for the fridge, microwave, dishwasher etc
  • Remove old circuit from the building signage - we don't have an illuminated sign
  • Install new lighting in Kitchen. Ceiling lights and under-cupboard lighting
  • Re-fit LoRaWAN gateway with power feed to upstairs cupboard
  • Replace UPS for the 3d printers - need to support a second printer
  • Replace batteries in data rack UPS
  • Install new radial circuit in the upstairs cupboard for fume extract and future data closet
  • Replace Workshop fluorescent tubes with LED low energy tubes
  • Replace Bay fluorescent lights with LED low energy lights
  • Install new ring main in the Workshop for the east wall, plus data cabling. Add points for lathe worklight and extractor fan
  • Tidy up old power and data cabling between Main room and Workshop
  • Replace Main room fluorescent lights with LED ceiling panels
  • Install new ring main for the electronics benches, plus data cabling
  • Remove wall-mounted extension leads from Workshop and fit metal-clad sockets on the ring main
  • Install 16A extention socket from bandsaw to center pillar for MIG welder use
  • Tidy up power for the Workshop inspection microscope
  • Replace Laser room fluorescent lights with LED ceiling panels
  • Replace Lobby fluorescent lights with LED ceiling panel
  • Install frost protection heaters in both toilets
  • Install fused outlet in Workshop for the auto dust extractor on the bandsaw

Reference Information

Distribution Board Schedules


Main Distribution Board, Merlin Gerin 3-phase, 63A / 30mA RCD
Circuit Type Rating Curve Icn Make Notes
1L1 MCB 6A B 10K Merlin Gerin Lobbby Lights
1L2 MCB 10A B 10K Merlin Gerin Loading Bay Lights
1L3 MCB 6A B 10K Merlin Gerin Mezanine Lights (Laser Room)
2L1 MCB 10A C 10K Merlin Gerin Toilet Frost protection heaters
2L2 MCB 20A B 10K Merlin Gerin Unknown
2L3 MCB 15A B 10K Merlin Gerin Data Rack
3L1 Not fitted
3L2 MCB 15A B 10K Merlin Gerin Fire Alarm
3L3 MCB 16A B 10K Merlin Gerin Emergency Stop Loop
4 MCB 15A B 6K Merlin Gerin 3-phase, Feed for DB3A, Drill Press & Grinder
5 MCB 20A B 10K Merlin Gerin 3-phase, Metal Lathe
6L1 MCB 10A B 10K Merlin Gerin Workshop Lights
6L2 MCB 32A B 6K Merlin Gerin Main Room Sockets
6L3 MCB 50A B 10K Merlin Gerin Feed to DB1A, Workshop sockets
Distribution Board DB1A, MEM Single Phase, 100A. On E-stop circuit
Circuit Type Rating Curve Icn Make Notes
1 30mA RCBO 32A C 10K MEM North and West Wall sockets
2 30mA RCBO 32A C 10K MEM Sockets on pillars
3 30mA RCBO 32A C 10K MEM East Wall sockets
4 30mA RCBO 16A C 10K MEM Bandsaw (shared with 16A Welder socket)
Distribution Board DB2A, MK Single Phase, 100A. Dual 30mA RCD board.
Circuit Type Rating Curve Icn Make Notes
1 MCB 40A B 6K MK Water Heater
2 MCB 16A B 6K MK Not used
3 MCB 20A C 6K Chint Upstairs heatpump
4 MCB 32A B 6K MK Not used
5 MCB 32A B 6K MK Not used
6 MCB 50A B 6K MK Feed for Kitchen board
7 MCB 16A C 6K Chint Kitchen and Workshop heat pumps
8 MCB 16A B 6K MK Not used
9 MCB 6A B 6K MK Main Room lights
10 MCB 6A B 6K MK Not used
Kitchen Distribution Board, BG single phase, 100A. Dual 30mA RCD board.
Circuit Type Rating Curve Icn Make Notes
1 MCB 40A B 6K BG Not used
2 MCB 32A B 6K BG Kitchen Sockets
3 MCB 32A B 6K BG Laser Room Sockets
4 MCB 16A B 6K BG Server closet
5 MCB 6A B 6K BG Not used (Main Room lights)
6 MCB 32A B 6K BG (For Main Room Sockets)
7 MCB 32A B 6K BG Electronics Benches
8 MCB 16A B 6K BG Fridge
9 MCB 6A B 6K BG Not used (Laser Room Lights)
10 MCB 6A B 6K BG Kitchen Lights